42

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Chapter 3 Wire Your Controller

Grounding Your Analog Cable

Use shielded communication cable (Belden #8761). The Belden cable has two
signal wires (black and clear), one drain wire, and a foil shield. The drain wire and
foil shield must be grounded at one end of the cable.

Expansion I/O Wiring

Digital Wiring Diagrams

The following illustrations show the digital expansion I/O wiring diagrams.

Figure 15 - 1762-IA8 Wiring Diagram

IMPORTANT

Do not ground the drain wire and foil shield at both ends of the
cable

Foil Shield

Black Wire

Drain Wire

Clear Wire

Insulation

44531

IN 7

IN 5

IN 3

IN 1

AC

COM

IN 6

IN 4

IN 2

IN 0

L1

L2

100/120V AC

AC

COM

Common
connected
internally.

44570