Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 353

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

313

MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F

Request

21 (0x15)

FC_DISABLE_UNSOLICITED

Yes

MicroLogix 1400 parses

Request

22 (0x16)

FC_ASSIGN_CLASS

No

Request

23 (0x17)

FC_DELAY_MEASURE

Yes

MicroLogix 1400 parses. Used for non-LAN

Request

24 (0x18)

FC_RECORD_CURRENT_TIME

No

Used for LAN

Request

25 (0x19)

FC_OPEN_FILE

Yes

MicroLogix 1400 parses

Request

26 (0x1A)

FC_CLOSE_FILE

Yes

MicroLogix 1400 parses

Request

27 (0x1B)

FC_DELETE_FILE

Yes

MicroLogix 1400 parses

Request

28 (0x1C)

FC_GET_FILE_INFO

No

Request

29 (0x1D)

FC_AUTHENTICATE_FILE

Yes

MicroLogix 1400 parses

Request

30 (0x1E)

FC_ABORT_FILE

No

Request

31 (0x1F)

FC_ACTIVATE_CONFIG

No

Request

32 (0x20)

FC_AUTHENTICATE_REQ

No

Request

33 (0x21)

FC_AUTHENTICATE_ERR

No

34 (0x22) to
128 (0x80)

No

Reserved.

Response

129 (0x81)

FC_RESPONSE

Yes

MicroLogix 1400 sends

Response

130 (0x82)

FC_UNSOLICITED_RESPONSE

Yes

MicroLogix 1400 sends

Response

131 (0x83)

FC_AUTHENTICATE_RESP

No

132 (0x84) to
255 (0xFF)

No

Reserved.

Function Codes for MicroLogix 1400 Series B Controllers

Message
Type

Function
Code

Name

MicroLogix
1400 Support

Description

Confirmation

0 (0x00)

FC_CONFIRM

Yes

MicroLogix 1400 parses/sends

Request

1 (0x01)

FC_READ

Yes

MicroLogix 1400 parses

Request

2 (0x02)

FC_WRITE

Yes

MicroLogix 1400 parses

Request

3 (0x03)

FC_SELECT

Yes

MicroLogix 1400 parses

Request

4 (0x04)

FC_OPERATE

Yes

MicroLogix 1400 parses

Request

5 (0x05)

FC_DIRECT_OPERATE

Yes

MicroLogix 1400 parses

Request

6 (0x06)

FC_DIRECT_OPERATE_NR

Yes

MicroLogix 1400 parses

Request

7 (0x07)

FC_IMMED_FREEZE

Yes

MicroLogix 1400 parses

Request

8 (0x08)

FC_IMMED_FREEZE_NR

Yes

MicroLogix 1400 parses

Request

9 (0x09)

FC_FREEZE_CLEAR

Yes

MicroLogix 1400 parses

Request

10 (0x0A)

FC_FREEZE_CLEAR_NR

Yes

MicroLogix 1400 parses

Request

11 (0x0B)

FC_FREEZE_AT_TIME

No

Request

12 (0x0C)

FC_FREEZE_AT_TIME_NR

No

Request

13 (0x0D)

FC_COLD_RESTART

Yes

MicroLogix 1400 parses. MicroLogix 1400 should not be in the
executing mode and any program and files should not be in
open state.

Function Codes for MicroLogix 1400 Series A Controllers

Message
Type

Function
Code

Name

MicroLogix
1400 Support

Description

Advertising