Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Chapter 3 Wire Your Controller

Figure 13 - Analog Output

Analog Channel Wiring Guidelines

Consider the following when wiring your analog channels:

• The analog common (COM) is connected to earth ground inside the

module. These terminals are not electrically isolated from the system. They
are connected to chassis ground.

• Analog channels are not isolated from each other.
• Use Belden 8761, or equivalent, shielded wire.
• Under normal conditions, the drain wire (shield) should be connected to

the metal mounting panel (earth ground). Keep the shield connection to
earth ground as short as possible.

• To ensure optimum accuracy for voltage type inputs, limit overall cable

impedance by keeping all analog cables as short as possible. Locate the I/O
system as close to your voltage type sensors or actuators as possible.

• The controller does not provide loop power for analog inputs. Use a power

supply that matches the transmitter specifications as shown below.