Rules for file authentication – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 331

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

291

MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F

Rules for File Authentication

The File Authentication process is optional, and unnecessary when the master
password of the downloaded ladder program is not configured.

When the password in the ladder program is configured by
RSLogix 500/RSLogix Micro, the DNP3 master sends a request with the
function code AUTHENTICATE_FILE (29) to authenticate permission before
file operation.

The object g70v2 is used for File Authentication, with two parameters:

• Username — from the Processor Name in the Controller Properties dialog

in RSLogix 500/RSLogix Micro

• Password — from the Master Password in the Controller Properties dialog

in RSLogix 500/RSLogix Micro.

In the example below, Username is "DNP3_A" and Password is "12345"(*****).

IMPORTANT

RSLogix 500/RSLogix Micro v8.30.00 and the MicroLogix 1400 Series
B controller support the opening of *.IMG files. However, some
information is not stored into the IMG file, for example, rung
comments. Be sure to store your ladder program in the RSLogix Files
(*.RSS) format before generating RSLogix IMG Files (*.IMG).

Advertising