309

MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F

For the elements of the DNP3 Slave Application Layer diagnostic counter
element offset 60 to 74, the counter values available with the structured display
in RSLogix 500/RSLogix Micro software as below.

18

ERR_PACKET_RELEASE

Firmware use only

19-29

Reserved

-

30

ERR_CONN_REJECTED

Incoming Connection is rejected by the IP address validation.

31

ERR_INVALID_HEADER_CRC

Received packet header has invalid CRC.

32

ERR_INVALID_HEADER

Received packet header has invalid packet format.

33

ERR_INVALID_PACKET_CRC

Received packet has invalid CRC.

34

ERR_BAD_PACKET_RECEIVED

Received packet is unknown.

35

ERR_PACKET_REJECTED

Received packet is rejected.

36

ERR_CONNECTION_BROKEN

The connection has been broken for some reason.

37-49

Reserved

-

50

ERR_INVALID_IP_ADDRESS

Target IP Address is invalid.

51

ERR_INVALID_PORT

Target Port Number is invalid.

52-

Reserved

-