143

Specifications Appendix A

Common mode rejection

(2)

> 55 dB at 50 and 60 Hz

> 55 dB at 50 and 60 Hz

>110 dB at 50 Hz (with 10 or
50 Hz filter)
>110 dB at 60 Hz (with 10 or
60 Hz filter)

>110 dB at 50 Hz (with 10 or
50 Hz filter)
>110 dB at 60 Hz (with 10 or
60 Hz filter)

Non-linearity (in percent full
scale)

±0.12%

(4)

±0.12%

(4)

±0.05% NA

Typical overall accuracy

(3)

±0.55% full scale at
-20…65 °C

(4)

±0.3% full scale at 25 °C

±0.32% full scale at
-20…65 °C

(4)

±0.24% full scale at 25 °C

±0.5 °C (F °) for Pt 385

NA

Input impedance

Voltage Terminal: 200 K

Ω

Current Terminal: 250

Ω

Voltage Terminal: 200 K

Ω

Current Terminal: 275

Ω

>10

ΜΩ

>10

ΜΩ

Current input protection

±32 mA

±32 mA

NA

NA

Voltage input protection

±30V

±30V

NA

NA

Channel diagnostics

Over or under range or open
circuit condition by bit
reporting for analog inputs.

Over or under range or open
circuit condition by bit
reporting for analog inputs.

Over or under range or open
circuit condition by bit
reporting for analog inputs.

Over or under range or open
circuit condition by bit
reporting for analog inputs.

(1) For proper operation, both the plus and minus input terminals must be within ±27V (±10V for 1762-IT4) of analog common.

(2) V

cm

= 1 V

pk-pk

AC

(3) V

cm

= 0 (includes offset, gain, non-linearity and repeatability error terms)

(4) Only applicable to Series B I/O modules.

Input Specifications

Specification

1762-IF2OF2

1762-IF4

1762-IR4

1762-IT4

Advertising