Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Appendix D Using ControlFLASH to Upgrade Your Operating System

This error message is displayed if the ControlFLASH tool is unable to match the
processor to the catalog number that was selected in the Catalog Number dialog
box.

To clear this error:

1. Click the OK button to go to the Catalog Number dialog box.
2. Select the correct catalog number in the dialog box, and proceed with the

update.

3. Restart the firmware upgrade procedure as described in the section Using

ControlFLASH for Firmware Upgrade on page 169.

Target Module Not in Proper State for Programming

This error message is displayed when the target module is not in a proper state for
programming.

To clear this error:

1. Put the controller in the PROGRAM mode.
2. Restart the firmware upgrade procedure as described in the section Using

ControlFLASH for Firmware Upgrade on page 169. If the error occurs
again, cycle power and restart the firmware upgrade process.

Failed to Receive Initial TFTP Request from Target

This error message is displayed when the initial TFTP request is not received.