Dh-485 configuration parameters, Devices that use the dh-485 network – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 228

Advertising
background image

188

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Appendix E Connecting to Networks via RS-232/RS-485 Interface

• maximum network segment of 1,219 m (4,000 ft.)

The DH-485 protocol supports two classes of devices: initiators and responders.
All initiators on the network get a chance to initiate message transfers. To
determine which initiator has the right to transmit, a token passing algorithm is
used.

Control of message transfers on the DH-485 network is performed by rotating
the token along the nodes on the network. A node holding the token can send a
message onto the network. Each node is allowed a fixed number of transmissions
(based on the Token Hold Factor) each time it receives the token. After a node
sends a message, it passes the token to the next device.

The allowable range of node addresses is 1…31. There must be at least one
initiator on the network (such as a MicroLogix controller, or an SLC 5/02 or
later processor).

DH-485 Configuration Parameters

When MicroLogix communications are configured for DH-485, the following
parameters can be changed:

See

Software Considerations on page 191

for tips on setting the parameters listed

above.

Devices that use the DH-485 Network

In addition to the MicroLogix controllers, the devices shown in the following
table also support the DH-485 network

.

DF1 Full-Duplex Configuration Parameters

Parameter

Options

Baud Rate

9600, 19.2K

Node Address

1…31 decimal

Token Hold Factor

1…4

Devices that Support DH-45 Network

Catalog
Number

Description

Installation

Function

Publication

Bulletin 1761
Controllers

MicroLogix 1000 Series C or later

These controllers support DH-485 communications.

1761-6.3

Bulletin 1762

MicroLogix 1200 Series A or later

These controllers support DH-485 communications.

1762-UM001

Bulletin 1763

MicroLogix 1100 Series A or later

These controllers support DH-485 communications.

1763-UM001

Bulletin 1764

MicroLogix 1500 Series A or later

These controllers support DH-485 communications.

1764-UM001

Bulletin 1747
Processors

SLC 500
Processors

SLC Chassis

These processors support a variety of I/O requirements and functionality.

1747-UM011

Advertising
This manual is related to the following products: