B - replacement parts, Micrologix 1400 replacement kits, Lithium battery (1747-ba) – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 191: Installation, Replacement parts, Appendix

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

151

Appendix

B

Replacement Parts

This chapter contains the following information:

• a table of MicroLogix 1400 replacement parts
• procedure for replacing the lithium battery

MicroLogix 1400
Replacement Kits

The table below provides a list of replacement parts and their catalog number.

Lithium Battery (1747-BA)

Installation

Follow the procedure below to ensure proper replaceable battery installation.

1. Insert a battery into the battery pocket with wires facing up.
2. Insert the battery wire connector into the battery connector.
3. Secure the battery connector wires around the 1762 expansion bus

connector as shown below.

Description

Catalog Number

Lithium Battery (See page 151.)

1747-BA

IMPORTANT

When the controller’s Battery Low indicator is lit, check whether
the battery wire connector is connected correctly or replace the
replaceable battery with a new one immediately. When the
indicator turns on, it means that either the battery is
disconnected, or that the battery requires replacement. The
controller is designed to operate for up to 2 weeks, from the time
that the indicator first turns on. We recommend that you replace
the battery immediately when the indicator turns on.

Advertising