Watson-Marlow MM440 User Manual

Page 109

Advertising
background image

Issue 10/06

3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

109

A high thermal motor load and when the line supply is frequently switched-
out/switched-in requires, for closed-loop vector control

− that a KTY84 sensor is used, or
− an external 24V power supply voltage is connected

Motor cooling

(Selects motor cooling system used)

0 Self-cooled: Using shaft mounted fan attached to motor
1 Force-cooled: Using separately powered cooling fan

2 Self-cooled and internal fan

3 Force-cooled and internal fan

Motor temperature sensor
Selects the motor temperature sensor.

0 No sensor
1 PTC thermistor (PTC)
2 KTY84
When "no sensor" or "PTC thermistor (PTC)“ is selected, the motor temperature is
determined on the basis of the value estimated by the thermal motor model.

r0631

ADC

5 V

Signal

loss

detection

T

1

= 4 s

2

1

No sensor
PTC
KTY

0

P0604

Fault

F0015

&

P0601 = 2

Thermal

motor

model

r0633

r0632

r0035

1

Motor
temp.

reaction

P0610

P0601

Equivalent

circuit data

P

V,mot

Power dissipation

V

ϑ

0

1

0

1

r0052

Bit13

PTC
KTY

Alarm threshold, motor overtemperature
Defines the alarm threshold for the motor overtemperature protection. This threshold, where
either a shutdown (trip) or Imax reduction is initiated (P0610) always lies 10 % above the
alarm threshold.

ϑ

warn

:

ϑ

trip

: Trip threshold (max. permissible temperature)

P0604

1.1

1.1

warn

trip

=

=

ϑ

ϑ

Warning threshold (P0604)

The alarm threshold should be at least 40 °C greater than the ambient temperature P0625.

P0604

≥ P0625 + 40 °C

Inverter temperature reaction
Defines reaction when motor temperature reaches warning threshold.
0 No reaction, warning only
1 Warning and I

max

reduction (results in a lower output frequency)

2 Warning and trip (F0011)

Motor overload factor [%]
Defines motor overload current limit in [%] relative to p0305 (rated motor current). Limited to
maximum inverter current or to 400 % of rated motor current (p0305), whichever is the
lower.

2

0

P0601 = ...

P0604 = ...

130.0 °C

P0610 = ...

0

P0335 = ...

p0640 = ...

150.0 %

Advertising