Issue 10/06

3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

209

Chopper

control

B-

B+

R

P1237 = 1

(5 %)

Chopper

control

B-

B+

R

P1237 = 3

(20 %)

R

R

R

Fig. 3-79

Increasing the level of braking energy which can be absorbed

The continuous power and the load duty cycle are modified using parameter P1237
(setting values, refer to Fig. 3-80a). If the load duty cycle monitoring switches from
the peak power (100%) to the continuous power, then this is dissipated for an
unlimited length of time in the braking resistor (refer to Fig. 3-80b). Contrary to the
braking resistor, as listed in Catalog DA51.2, the chopper control can be
permanently operated with 100% power.

t

t

cycle

P

DB

P

100

t

ON

t

OFF

P1237

t

ON

t

OFF

t

cycle

P

DB

5 %

12.0

228.0

240.0

0.05

10 %

12.6

114.0

126.6

0.10

20 %

14.2

57.0

71.2

0.20

50 %

22.8

22.8

45.6

0.50

100 % Infinite

0 Infinite

1.00

t

t

cycle

P

DB

P

100

t

100

t

P1237

t

OFF

a

b

Fig. 3-80

Chopper load duty cycle

For MICROMASTER 440, up to and including Size FS F, the braking module is
integrated in the drive inverter and the braking resistor can be connected via
external terminals B+, B-.