Watson-Marlow MM440 User Manual

Page 244

Advertising
background image

3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

244

6SE6400-5AW00-0BP0

The following criteria provide a basis as to when a speed actual value encoder is
required:
¾

High speed accuracy is required

¾

High requirements are placed on the dynamic response

♦ Improved control performance

♦ Improved immunity to disturbances

¾

The torque is to be controlled over a control range greater than 1:10

¾

A defined and/or a changing torque has to be maintained for speeds below

approx. 10 % of the rated motor frequency P0310

When it comes to entering a setpoint, the Vector control (refer to Table 3-40) is
sub-divided into
¾

Closed-loop speed control, and

¾

Closed-loop torque/current control (briefly: Closed-loop torque control).

Table 3-40

Vector control versions

Vector control (closed-loop)

Without encoder

With encoder

Closed-loop speed control

P1300 = 20, P1501 = 0

P1300 = 21, P1501 = 0

Closed-loop torque control

P1300 = 20, P1501 = 1

P1300 = 22

P1300 = 21, P1501 = 1

P1300 = 23


When closed-loop speed control is used, the closed-loop torque control is
secondary. This type of cascaded closed-loop control has proven itself in practice
regarding commissioning and increased transparency.

Advertising