3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

246

6SE6400-5AW00-0BP0

¾

Closed-loop controlled operation down to

≈ 1 Hz

¾

Can start in the closed-loop controlled mode (immediately after the drive has

been energized)

¾

The low frequency range (0 Hz) is passed-through in closed-loop controlled

operation

f

t

P1755

Closed loop

Open loop

Start

f

t

Closed loop

Open loop

Zero crossing

P1755

P1755

Fig. 3-103

Starting and passing-through 0 Hz in closed-loop controlled operation

The following advantages are obtained as a result of closed-loop controlled
operation down to approx. 1 Hz (this can be selected using parameter P1755) as
well as also the possibility to immediately start closed-loop controlled at 0 Hz or to
reverse closed-loop controlled (this can be set using parameter P1750):
¾

No changeover operation is required within the closed-loop control

(smooth behavior – no frequency dips)

¾

Continuous closed-loop speed-torque control is possible down to approx. 1 Hz.

NOTE
For closed-loop controlled reversing or closed-loop controlled starting from 0 Hz it
must be taken into account that when staying too long (> 2 s or > P1758) in the
range around 0 Hz, that the closed-loop control automatically changes-over from
closed-loop into the open-loop controlled mode.