3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

169

Contrary to "Direct selection + ON command", the ON command is only active if
the setting for the first 4 binary inputs is set to "Binary-coded selection + ON
command" or P0701 = P0702 = P0703 = P0704 = 17. The following is obtained
analog to the above example:
a) Standard method

→ P0701 = 17

b) BICO method

→ P0701 = 99, P1020 = 722.0, P1016 = 3

P1016

P0701 = 17 or P0701 = 99, P1020 = 722.0, P1016 = 3

DIN1

r0722.0

P1020

1

2,3

0

P0702 = 17 or P0702 = 99, P1021 = 722.1, P1017 = 3

P1017

DIN2

r0722.1

P1021

1

2,3

0

. .

. .

0 0 0

1

1 1 1

1

Festf requenz 15

-650.00 ... 650.00

[Hz]

P1015.D (65.00)

r1024

CO: Ist-

Festf req.

.
.
.

.

.

.

...

Festf requenz 1

-650.00 ... 650.00 [Hz]

P1001.D (0.00)

Fig. 3-50

Example for selecting FF1 via DIN1 and FF2 via DIN2 using the binary-coded
method