1 installation after a period of storage – Watson-Marlow MM440 User Manual

Page 23

Advertising
background image

Issue 10/06

2 Installation

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

23

2.1

Installation after a Period of Storage

Following a prolonged period of storage, you must reform the capacitors in the
inverter.

Frame Sizes A to F

100

50

75

0,5

1

[%]

2

4

6

8

Storage period less than 1 year:

Storage period 1 to 2 years:

Storage period 2 to 3 years:

Storage period 3 and more years:

No action necessary

Prior to energizing, connect to
voltage for one hour

Prior to energizing, form
according to the curve

Prior to energizing, form
according to the curve

Voltage

Time t [h]

Fig. 2-1

Forming

Frame Sizes FX and GX

Reforming the capacitors can be accomplished by applying 85% of the rated input
voltage for at least 30 minutes without load.