3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

73

3.2.4 Changing

parameters

using the operator panel

The way that parameter P0719 can be changed will now be described; please use
this description as a basis when setting all of the other parameters using the BOP.

Changing P0004 – parameter filter function

Step

Result on the display

1

Press

in order to access the parameter

2

Press

until P0004 is displayed

3

Press

in order to reach the parameter value

level

4

Press

or

in order to obtain the

required value

5

Press

to acknowledge the value and to save

the value

6

The user can only see the command parameters.


Changing an indexed parameter P0719 – selecting the command/frequency
setpoint

Step

Result on the display

1

Press

in order to access the parameter

2

Press

until P0719 is displayed

3

Press

in order to reach the parameter value

4

Press

in order to display the currently set

value

5

Press

or

in order to obtain the required

value

6

Press

to acknowledge the value and to save

the value

7

Press

until r0000 is displayed

8

Press

in order to return to the operating

display (the display which the customer has
defined)

Fig. 3-16

Changing parameters using the BOP

NOTE

The BOP sometimes display

when changing parameter values. This

means that the drive inverter is presently handling another higher-priority task.