Watson-Marlow MM440 User Manual

Page 128

Advertising
background image

3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

128

6SE6400-5AW00-0BP0

DIN4

Terminals

Sequence control

BOP

P0700[0] = 2

P0700[1] = 1

P0810 = 722.3

ADC

Setpoint

channel

MOP

0

1

P1000[0] = 2

P1000[1] = 1

Motor

control

0

1

Drive data set (DDS) bit 0
Selects the command source from which bit 0 should be read-out to select a drive data set.

t

0

1

2

3

(0:0)

BI: DDS bit 0

P0820

(0:0)

BI: DDS bit 1

P0821

t

0

1

2

3

CO/BO: Act CtrlWd2

r0055

r0055

CO/BO: Act CtrlWd2

r0055

r0055

.04

.04

.05

.05

r0051[1]

Active DDS

Select DDS

approx. 50 ms

approx. 50 ms

Changeover time

Changeover time

Operation

Ready

t

r0051 [2]

CO: Active DDS

.01

The currently active drive data set (DDS) is displayed using parameter r0051[1]:

r0055

bit05

r0054

bit04

1. DDS

0

0

2. DDS

0

1

3. DDS

1

0

3. DDS

1

1

r0051 [0]

0

1

2

2

r0051 [1]

0

1

2

2

Select

DDS

Active

DDS

Most frequent settings:
722.0 = Digital input 1 (P0701 must be set to 99, BICO)
722.1 = Digital input 2 (P0702 must be set to 99, BICO)
722.2 = Digital input 3 (P0703 must be set to 99, BICO)
722.3 = Digital input 4 (P0704 must be set to 99, BICO)
722.4 = Digital input 5 (P0705 must be set to 99, BICO)
722.5 = Digital input 6 (P0706 must be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, P0707 must be set to 99)
722.7 = Digital input 8 (via analog input 2, P0708 must be set to 99)

0

P0820 = ...

Advertising