3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

134

6SE6400-5AW00-0BP0

Reset to the factory setting


User access level
1 Access level, standard

Parameter filter
0 All parameters

Commissioning parameter
30 Factory

setting

Factory reset
1 Parameter reset to the default values

The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then
automatically
exits the reset menu and sets
P0970 = 0 :

Disabled

P0010 = 0 :

Ready

NOTE
When resetting the parameters to the factory setting, the communications memory
is re-initialized. This means that communications via USS as well as also via the
CB board are interrupted for the time it takes to make the reset:
¾

The connected PLC (e.g. SIMATIC S7) goes into stop

¾

The STARTER start-up program buffers the communications failure

¾

For the DriveMonitor start-up program, "NC" (not connected) or "drive busy" is

displayed.

¾

The "busy" text is displayed at the BOP operator panel

After reset has been completed, for the start-up programs STARTER and
DriveMonitor or the BOP operator panel, communications are automatically re-
established.

START

END

P0003 = 1

P0004 = 0

P0010 = 30

P0970 = 1

1

0

0

0