3 Functions
Issue 10/06
MICROMASTER 440 Operating Instructions
134
6SE6400-5AW00-0BP0
Reset to the factory setting
User access level
1 Access level, standard
Parameter filter
0 All parameters
Commissioning parameter
30 Factory
setting
Factory reset
1 Parameter reset to the default values
The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then
automatically
exits the reset menu and sets
P0970 = 0 :
Disabled
P0010 = 0 :
Ready
NOTE
When resetting the parameters to the factory setting, the communications memory
is re-initialized. This means that communications via USS as well as also via the
CB board are interrupted for the time it takes to make the reset:
¾
The connected PLC (e.g. SIMATIC S7) goes into stop
¾
The STARTER start-up program buffers the communications failure
¾
For the DriveMonitor start-up program, "NC" (not connected) or "drive busy" is
displayed.
¾
The "busy" text is displayed at the BOP operator panel
After reset has been completed, for the start-up programs STARTER and
DriveMonitor or the BOP operator panel, communications are automatically re-
established.
START
END
P0003 = 1
P0004 = 0
P0010 = 30
P0970 = 1
1
0
0
0