2 Installation

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

45

Frame Sizes D and E

The Gland Plate is factory fitted. If the installation conditions are restricted, the
shield of the motor cable can also be attached outside the cabinet, as shown in
Fig. 2-14, for example.Frame Sizes FX and GX

Frame size F

The gland plate for the control cables is factory-fitted.

Devices without filter: The shield of the motor cable must be attached outside the

cabinet, as shown in Fig. 2-14, for example.

Devices with filter:

The gland plate for the motor cable is factory-fitted.

Frame Sizes FX and GX

Connect the wire shields to the shield connection points shown in the connection
drawing (see Fig. 2-9 and Fig. 2-10) .

Twist the shields of the motor cables and screw them to the PE connection for the
motor cable.

When using an EMI filter, a power commutating choke is required. The wire shields
should be fastened to the metallic mounting surface as close as possible to the
components.