3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

84

6SE6400-5AW00-0BP0

P0010 = 1

Commissioning parameter *
0 Ready
1 Quick commissioning
30 Factory setting (refer to Section 3.5.9)

NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.

P0100 =...


P0100 = 1, 2

P0100 = 0

Europe/ North America
(enters the line supply frequency)
0 Europe [kW], frequency default 50 Hz
1 North America [hp], frequency default 60 Hz
2 North America [kW], frequency default 60 Hz
NOTE
For P0100 = 0 or 1, the setting of switch

DIP50/60

determines the value of

P0100 (refer to Section 3.5.1).

OFF = kW, 50 Hz
ON = hp, 60 Hz

Inverter application

(enters the required torque)

0 Constant torque (e.g. compressors, processing machines)
1 Variable torque (e.g. pumps, fans)
NOTE
This parameter is only effective for drive inverters

5.5 kW / 400 V

Select motor type
1 Asynchronous motor (induction motor)
2 Synchronous motor
NOTE
For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are
permitted.

P0304 =... P0304 =... Rated motor voltage

(Nominal motor voltage [V]
from rating plate)
The rated motor voltage on the rating
plate must be checked, regarding the
star/delta circuit configuration to
ensure that it matches with the circuit
connection configured at the motor
terminal board

P0305 =... P0305 =... Rated motor current

(Nominal motor current [A]
from rating plate)

P0307 =... P0307 =... Rated motor power

(Nominal motor power [kW/hp]
from rating plate)
If P0100 = 0 or 2, value will be in kW.
If P0100 = 1, value will be in in hp.

P0304

P0305

P0307

P0308 P0311

P0310

Example of a typical motor rating plate (data for
a delta circuit configuration).
The precise definition and explanation of this
data is specified in DIN EN 60 034-1.

P0308 =...

P0308 =...

Rated motor cosPhi
(Nominal motor power factor (cos

ϕ) from rating plate)

If the setting is 0, the value is automatically calculated
P0100 = 1,2: P0308 no significance, no entry required.

P0309 =...

P0309 =... Rated motor efficiency

(Nominal motor efficiency in [%] from rating plate)
Setting 0 causes internal calculation of value.
P0100 = 0: P0309 no significance, no entry required.

1

0

P0300 =... P0300 =...

P0205 =... P0205 =...

0

0

FU-spec.

FU-spec.

FU-spec.

FU-spec.

FU-spec.