2 Installation

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

25

Atmospheric Pollution

Do not install the inverter in an environment, which contains atmospheric pollutants
such as dust, corrosive gases, etc.

Water

Take care to site the inverter away from potential water hazards, e.g. do not install
the inverter beneath pipes that are subject to condensation. Avoid installing the
inverter where excessive humidity and condensation may occur.

Installation and cooling

CAUTION

The inverters MUST NOT be mounted horizontally.

The inverters can be mounted without any clearance at either side. When mounting
inverters one above the other, the specified environmental conditions must not be
exceeded.

Independent of this, these minimum distances must be observed.
¾ Frame Size A, B, C above and below 100 mm
¾ Frame Size D, E

above and below 300 mm

¾ Frame Size F

above and below 350 mm

¾ Frame Size FX, GX above 250 mm

below 150 mm

in front 40 mm (FX), 50 mm (GX)

No equipment that could have a negative effect on the flow of cooling air should be
installed in this area. Make sure that the cooling vents in the inverter are positioned
correctly to allow free movement of air.