3.23.1.2 Slip

compensation

Parameter range:

P1335

Warnings -
Faults -
Function chart number:

FP6100

In the V/f characteristic operating mode the motor frequency is always lower than
the drive inverter output frequency by the slip frequency f

s

. If the load (the load is

increased from M

1

to M

2

) is increased with a constant output frequency, then the

slip s when motoring increases and the motor frequency decreases (from f

1

to f

2

).

This behavior, typical for an induction motor, can be compensated using slip
compensation P1335. This therefore eliminates the speed reduction, caused by the
load, by boosting (increasing) the drive inverter output frequency (refer to Fig.
3-98).

Without Slip compensation

M

f

∆f

f

2

f

1

M

2

M

1

With Slip compensation

M

f

∆f

f

2

f

1

M

2

M

1

f

out M1

f

out M2

Fig. 3-98

Slip compensation