16 automatic restart – Watson-Marlow MM440 User Manual

Page 211

Advertising
background image

Issue 10/06

3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

211

3.16 Automatic

restart

Parameter range:

P1210

P1211

Warnings A0571
Faults F0035
Function chart number:

-

After a power failure (F0003 "Undervoltage"), the "Automatic restart" function
(enabled using P1210) automatically powers-up the drive inverter again. Any faults
are automatically acknowledged by the drive inverter.
When it comes to power failures (line supply failure), then a differentiation is made
between the following conditions:

Line undervoltage (brownout)

"Line undervoltage" is a situation where the line supply is interrupted and returns
before (if installed) the BOP display has gone dark (this is an extremely short line
supply interruption where the DC link hasn't completely collapsed).

Line failure (blackout)

"Line failure" is a situation where the display has gone dark (this represents a
longer line supply interruption where the DC link has completely collapsed) before
the line supply returns.
The automatic restart function P1210 is shown in the following diagram (refer to
Fig. 3-81) as a function of external states / events.

0

1

2

+

3

+

+

+

+

4

+

+

5

+

+

+

6

+

+

+

+

+

Fault acknowl.

Fault acknowl.

Fault acknowl.

Fault acknowl.

Fault acknowl.

Fault acknowl.

restart

restart

restart

restart

restart

Fault acknowl.

Fault acknowl.

Fault acknowl.

restart

restart

Fault acknowl.

Fault acknowl.

Fault acknowl.

restart

restart

restart

Fault acknowl.

Fault acknowl.

restart

restart

Fault acknowl.

Fault acknowl.

Fault acknowl.

restart

restart

restart

ON always active (permanent)

P1210

ON in no-voltage condition

Fault F0003 on

All other faults on

Brownout

Blackout

Brownout

Blackout

All faults on

Blackout

Restart

No faults on

Blackout

+

Fault acknowl.

restart

Fault acknowl.

Restart

Restart

Fig. 3-81

Automatic restarts

Advertising