3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

217

NOTE
¾

If the DC link voltage exceeds the power-on threshold r1242 (switch-on level of

Vdc_max.) of the Vdc_max controller in the "Ready" state, then the Vdc_max
controller is de-activated and warning A0910 is output.

Cause:

The line supply voltage does not match the application situation.

Remedy: Refer to parameters P1254 and P0210.

¾

If, in the "Run" state, the DC link voltage exceeds the power-on threshold r1242

and if the Vdc_max controller output is limited by parameter P1253 for approx.
200 ms, then the Vdc_max controller is de-activated and warning A0910 and,
where relevant, fault F0002 are output.

Cause:

Line supply voltage P0210 or ramp-down time P1121 too low

The moment of inertia of the driven load is too high

Remedy: Refer to parameters P1254, P0210, P1121

Use a braking resistor

¾

The Vdc_max switch-in threshold V

DC_max

depends on P1254

V

DC_max

(P1254 = 0)

V

DC_max

(P1254

0)

a) Auto-detect function enabled (P1254 = 1):

- V

DC_max

(P1254 = 1) is automatically calculated when the drive inverter

runs-up, i.e. after the line supply voltage has been connected

- Using the auto-detect function, the V

DC-Comp

threshold automatically

adapts itself to the line supply voltage at the particular installation
location.

b) Auto-detect function disabled (P1254 = 0):

-

0210

P

2

15

.

1

U

max

_

DC

=

- The

V

DC-Comp

threshold is immediately re-calculated after entering P0210

- P0210 must be adapted to the particular installation location.