1 universal serial interface (uss) – Watson-Marlow MM440 User Manual

Page 146

Advertising
background image

3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

146

6SE6400-5AW00-0BP0

NOTE
¾

A communications (CB) module as well as a programming / operator unit can

be simultaneously connected to the COM link interface via terminals 29/30
(USS). This is the reason that the communications module has priority over
USS. In this case, the USS node (USS station) via the COM link is de-activated.

¾

Contrary to PROFIBUS, the RS485 port (terminals 29/30) is not optically isolated

(not floating). When installing the system, it must be ensured that EMC faults do
not result in communication failures or damage to the RS485 drivers.

3.7.1

Universal serial interface (USS)

Parameter range:

P2009 – r2037

Significance

COM link

BOP link

USS basic setting

USS baud rate

P2010[0]

P2010[1]

USS

address

P2011[0]

P2011[1]

USS-PZD

length

P2012[0]

P2012[1]

USS-PKW

length

P2013[0]

P2013[1]

PZD data

Received

data

r2018[8]

r2015[8]

Received control word 1

r2036

r2032

Received control word 2

r2037

r2033

Sent

data

P2019[8]

P2016[8]

Sent status word 1

r0052

r0052

Sent status word 2

r0053

r0053


Alarms: ---
Faults: F0071,

F0072

Function chart number: FP2500, FP2510, FP2600, FP2610
Features:

− electrical features: Not electrically isolated

USS at the BOP link with PC-

converter connecting set

Not electrically isolated

USS at COM link

(terminals 29 /30)

− cycle time (MM440): 8 ms

(process data PZD)

Background (parameter ID value PKW)