1 50/60 hz setting – Watson-Marlow MM440 User Manual

Page 79

Advertising
background image

Issue 10/06

3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

79

3.5.1

50/60 Hz setting

The frequency setting made in the factory can be adapted to the North American
market, without requiring any parameterization using an operator panel or PC tool
using the DIP50/60 switch (refer to Fig. 3-21) under the I/O board (refer to the
Appendix C when removing the I/O board).

Rem

ov

e I

/O

board

DIP50/60

Fig. 3-21

DIP switch to change-over between 50/60 Hz

The switch determines the value of parameter P0100 corresponding to the
following diagram (refer to Fig. 3-22). Besides P0100 = 2, after the power supply
voltage has been switched-in, the DIP50/60 switch determines the 50/60 Hz setting
(value of parameter P0100).

P0100 = 2

?

P0100 = 0

P0100 = 2

P0100 = 1

P0100 = 2

?

P0100 = 1

?

yes

yes

no

no

yes

yes

no

no

Quick

commissioning

P0010 = 1

Power

cycle

DIP2 = OFF

?

Power in kW

Frequency 50 Hz

Power in kW

Frequency 60 Hz

Power in hp

Frequency 60 Hz

Fig. 3-22

Mode of operation of the DIP50/60 switch in conjunction with P0100