Watson-Marlow MM440 User Manual

Page 267

Advertising
background image

Issue 10/06

5 MICROMASTER 440 specifications

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

267

Input voltage range

1 AC 200 V – 240 V. ± 10 %

(Unfiltered)

Order No.

6SE6440- 2UC11

-2AA1

2UC12

-5AA1

2UC13

-7AA1

2UC15

-5AA1

2UC17

-5AA1

2UC21

-1BA1

2UC21

-5BA1

2UC22

-2BA1

2UC23

-0CA1

[kW]

0.12 0.25 0.37 0.55

0.75 1.1 1.5 2.2 3.0

Output Rating (CT)

[hp]

0.16

0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0

Output Power

[kVA]

0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0

CT Input Current 1)

[A]

1.8 3.2 4.6 6.2 8.2 11.0

14.4

20.2

35.5

CT Output Current

[A]

0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4

13.6

Fuse [A]

10 10 10 16 16 20 20 32 40

Recommended 3NA

3803 3803 3803 3805 3805 3807 3807 3812 3817

for UL specified

* * * * * * * * *

[mm

2

]

1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0 6.0

Input Cable Min.

[awg]

18 18 18 16 16 14 14 12 10

[mm

2

]

2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0

Input Cable Max.

[awg]

14 14 14 14 14 10 10 10 8

[mm

2

]

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5

Output Cable Min.

[awg]

18 18 18 18 18 18 18 18 16

[mm

2

]

2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0

Output Cable Max.

[awg]

14 14 14 14 14 10 10 10 8

[kg]

1.3 1.3 1.3 1.3 1.3 3.3 3.3 3.3 5.5

Weight

[lbs]

2.9 2.9 2.9 2.9 2.9 7.3 7.3 7.3 12.1

Input voltage range

3 AC 200 V – 240 V. ± 10 %

(with built in Class A Filter)

Order No.

6SE6440- 2AC23-

0CA1

2AC24-

0CA1

2AC25-

5CA1

[kW]

3.0 4.0 5.5

Output Rating (CT)

[hp]

4.0 5.0 7.5

Output Power

[kVA]

6.0 7.7 9.6

CT Input Current 1)

[A]

15.6 19.7 26.5

CT-Output Current

[A]

13.6 17.5 22.0

VT Input Current 1)

[A]

- 28.3 34.2

VT-Output Current

[A]

- 22.0 28.0

Fuse [A]

25 32 35

Recommended 3NA

3810 3812 3814

for UL specified

* * *

[mm

2

]

2.5 4.0 4.0

Input Cable Min.

[awg]

14 12 12

[mm

2

] 10.0 10.0 10.0

Input Cable Max.

[awg]

8 8 8

[mm

2

]

1.5 4.0 4.0

Output Cable Min.

[awg]

16 12 12

[mm

2

] 10.0 10.0 10.0

Output Cable Max.

[awg]

8 8 8

[kg]

5.7 5.7 5.7

Weight

[lbs]

12.5 12.5 12.5

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply V

k

= 2 % referred to the rated drive converter power and a rated line supply voltage

of 240 V without line commutating reactor.

* UL listed fuses such as Class NON from Bussmann are required for use in America

Advertising