2 interconnecting signals (bico technology) – Watson-Marlow MM440 User Manual

Page 57

Advertising
background image

Issue 10/06

3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

57

3.1.2 Interconnecting

signals (BICO technology)

A state-of-the-art drive unit must be able to interconnect internal and external
signals (setpoint / actual values and control / status signal). This interconnection
functionality must have a high degree of flexibility in order to be able to adapt the
drive to new applications. Further, a high degree of usability is required, which also
fulfills standard applications. This is the reason that within the MICROMASTER
series of drive units, BICO technology (

→ flexibility) and fast parameterization

using parameters P0700 / P1000 (

→ usability) or P0719 (→ combination

P0700/P1000) have been introduced to be able to fulfill both of these requirements.

3.1.2.1

Selecting the command source P0700 / selecting the setpoint
source P1000

The following parameters can be used to quickly interconnect setpoints and control
signals:
¾

P0700 "Selection of command source"

¾

P1000 "Selection of setpoint source"

These parameters are used to define via which interface the drive inverter receives
the setpoint or the power-on/power-off command. The interfaces, listed in Table
3-2 can be selected for the command source P0700.

Table 3-2

Parameter P0700

Parameter values Significance / command source

0

Factory default

1

BOP (operator panel, refer to Section 3.2.1)

2

Terminal strip

4

USS on BOP link

5

USS on COM link

6

CB on COM link


The following internal or external sources / interfaces can be selected for the
frequency setpoint source P1000. In addition to the main setpoint (1

st

position), a

supplementary setpoint (2

nd

position) can be selected (refer to Table 3-3).

Advertising