5 MICROMASTER 440 specifications

Issue 10/06

MICROMASTER 440 Operating Instructions

266

6SE6400-5AW00-0BP0

Table 5-4

Data for braking resistors

I

DC_max

for Frame Size

Rated voltage

V

DC_max

A B

C

D E F

230 V

410 - 420 V

2,33 A

(180

Ω)

6,18 A

(68

Ω)

10,77 A (39

Ω)

15,56 A (27

Ω)

41,0 A

(10

Ω)

60,3 A

(6,8

Ω)

124,2 A

(3,3

Ω)

400 V

820 - 840 V

2,15 A

(390

Ω)

5,25 A

(160

Ω)

15 A

(56

Ω)

30,4 A

(27

Ω)

54,7 A

(15

Ω)

100,0 A

(8,2

Ω)

575 V

1020 V

-

-

8,5 A (120

Ω)

12,4 A (82

Ω)

26,2 A

(39

Ω)

37,8 A

(27

Ω)

85,0 A
(12

Ω)


Table 5-5

MICROMASTER 440 Specifications

In order that the system is in compliance with UL, UL-certified fuses must be
used with the appropriate rated current.

Input voltage range

1 AC 200 V – 240 V, ± 10 %

(with built in Class A Filter)

Order No.

6SE6440- 2AB11

-2AA1

2AB12

-5AA1

2AB13

-7AA1

2AB15

-5AA1

2AB17

-5AA1

2AB21

-1BA1

2AB21

-5BA1

2AB22

-2BA1

2AB23

-0CA1

[kW]

0.12 0.25 0.37 0.55

0.75 1.1 1.5 2.2 3.0

Output Rating (CT)

[hp]

0.16

0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0

Output Power

[kVA]

0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0

CT Input Current 1)

[A]

1.8 3.2 4.6 6.2 8.2 11.0

14.4

20.2

35.5

CT Output Current

[A]

0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4

13.6

Fuse [A]

10 10 10 16 16 20 20 32 40

Recommended 3NA

3803 3803 3803 3805 3805 3807 3807 3812 3817

for UL specified

* * * * * * * * *

[mm

2

]

1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0 6.0

Input Cable Min.

[awg]

18 18 18 16 16 14 14 12 10

[mm

2

]

2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0

Input Cable Max.

[awg]

14 14 14 14 14 10 10 10 8

[mm

2

]

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5

Output Cable Min.

[awg]

18 18 18 18 18 18 18 18 16

[mm

2

]

2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0

Output Cable Max.

[awg]

14 14 14 14 14 10 10 10 8

[kg]

1.3

1.3 1.3 1.3 1.3 3.4 3.4 3.4 5.7

Weight

[lbs]

2.9

2.9 2.9 2.9 2.9 7.5 7.5 7.5 12.5

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply V

k

= 2 % referred to the rated drive converter power and a rated line supply voltage

of 240 V without line commutating reactor.

* UL listed fuses such as Class NON from Bussmann are required for use in America