5 classification of emc performance, Class 1: general industrial, Class 2: industrial application with filter – Watson-Marlow MM440 User Manual

Page 278

Advertising
background image

7 Electro-magnetic compatibility

Issue 10/06

MICROMASTER 440 Operating Instructions

278

6SE6400-5AW00-0BP0

7.1.5

Classification of EMC performance

General classes of EMC performance are available as detailed below:

Class 1: General Industrial

Compliance with European Standard EN 61800-3 (EMC Product Standard for
Power Drive Systems) for use in Second Environment (Industrial).

Table 7-2

General industrial application

EMC Phenomenon

Standard

Level

Radiated emissions

EN 55011

Level A1

Emissions:

Conducted emissions

EN 61800-3

Limits complying with EN 55011,
Class A, Group 2

Electrostatic discharge

EN 61000-4-2

8 kV air discharge

Burst interference

EN 61000-4-4

2 kV power cables,

1 kV control cables

Immunity:

Radio-frequency
electromagnetic field

EN 61000-4-3

26–1000 MHz, 10 V/m

Class 2: Industrial application with filter

This level of EMC performance will allow the manufacturer/installer to certify their
equipment themselves for compliance with the EMC directive for the industrial
environment, as far as the EMC performance characteristics of the power drive
system are concerned. Performance limits are as specified in the Generic Industrial
Emissions and Immunity Standards EN 61000-6-4 und EN 61000-6-2.

Table 7-3

With filter, for industrial applications

EMC Phenomenon

Standard

Level

Radiated emissions

EN 55011

Level A1

Emissions:

Conducted emissions

EN 61800-3

Limits complying with EN 55011,
Class A, Group 2

Supply voltage distortion

EN 61000-2-4

Voltage fluctuations, dips,
unbalance, frequency
variations

EN 61000-2-1

Magnetic fields

EN 61000-4-8

50 Hz, 30 A/m

Electrostatic discharge

EN 61000-4-2

8 kV air discharge

Burst interference

EN 61000-4-4

2 kV power cables,

2 kV control cables

Radio-frequency electro-
magnetic field, amplitude-
modulated

EN 61000-4-3

80–1000 MHz, 10 V/m, 80% AM,
power and signal lines

Immunity:

Radio-frequency electro-
magnetic field, pulse-
modulated

EN 61000-4-3

900 MHz, 10 V/m 50 % duty cycle,
repetition rate 200 Hz

Advertising