4 digital output (dout) – Watson-Marlow MM440 User Manual

Page 99

Advertising
background image

Issue 10/06

3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

99

DIN channel (e.g. DIN1 - PNP (P0725 = 1))

24 V

T

0

&

0

1

PNP/NPN DIN

0 ... 1

P0725 (1)

0 V

24 V

Debounce time: DIN

0 ... 3

P0724 (3)

CO/BO: Bin.inp.val

r0722

r0722

.0

Kl.9
P24 (PNP)
Kl.28
0 V (NPN)

Pxxxx BI: ...

P0701

Function

0

1

3.5.7.4

Digital output (DOUT)

BI: Function of digital output 1 *
Defines source of digital output 1.

BI: Function of digital output 2 *
Defines source of digital output 2.

BI: Function of digital output 3 *
Defines source of digital output 3.

Invert digital output
Defines high and low states of relay for a
given function.

Common Settings:
52.0 Drive ready

0

52.1 Drive ready to run

0

52.2 Drive running

0

52.3 Drive fault active

0

52.4 OFF2 active

1

52.5 OFF3 active

1

52.6 Switch on inhibit active

0

52.7 Drive warning active

0

52.8 Deviation, setpoint / actual value

1

52.9 Control from PLC (PZD control)

0

52.A Maximum frequency reached

0

52.B Alarm: Motor current limiting

1

52.C Motor holding brake (MHB) active

0

52.D Motor overload

1

52.E Motor direction of rotation, clockwise 0
52.F Frequency inverter overload

1

53.0 DC brake active

0

.

(52:3)

BI: Fct. of DOUT 1

P0731.C

-1

0

1

Invert DOUTs

0 ... 7

P0748 (0)

CO/BO: State DOUTs

r0747

r0747

Kl.20

Kl.18

.0

Function

xxxx.y

rxxxx.y

P0731 = xxxx.y

DOUT channel

Relay :

DC 30 V / 5 A
AC 250 V / 2 A

Kl.28

Kl.9

int. 24 V
max. 100 mA

NO

COM

NC

Kl.19

or

Text

max. opening / closing time

5 / 10 ms

52.3

0

P0731 = ...

52.7

0.0

P0748 = ...

P0733 = ...

P0732 = ...

Advertising