3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

188

6SE6400-5AW00-0BP0

OFF3

The braking characteristics of OFF3 are identical with those of OFF1 with the
exception of the autonomous OFF3 ramp-down time P1135. If the output frequency
falls below parameter value P2167 and if the time in P2168 has expired, then the
inverter pulses are cancelled as for the OFF1 command.

t

P2168

t

P2167

Operation

act

f

OFF3

P1082

f

max

r0052 Bit02

P1135

P1082

f

P1135

t

2

3

AUS

,

down

=

t

down,AUS3

Pulse

ncellation

f

2

Fig. 3-66

OFF3

NOTE
OFF3 can be entered using a wide range of command sources via BICO
parameters P0848 (BI: 1. OFF3) and P0849 (BI: 2. OFF3).
¾

OFF3 is low active

¾

When simultaneously selecting the various OFF commands, the following

priority applies: OFF2 (highest priority) – OFF3 – OFF1