3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

54

6SE6400-5AW00-0BP0

Attribute

group

Attribute Description

The parameters are sub-divided into groups according to their functionality. This
increases the transparency and allows a parameter to be quickly searched for.
Furthermore, parameter P0004 can be used to control the ability to be visualized for
the BOP / AOP.
Main

parameter

area:

ALWAYS 0

all

parameters

INVERTER

2 drive inverter parameters

0200 .... 0299

MOTOR

3 motor parameters

0300 .... 0399 and

0600 .... 0699

ENCODER

4 speed encoder

0400 .... 0499

TECH_APL

5 technical applications / units

0500 .... 0599

COMMANDS 7 control commands, digital I/O

0700 .... 0749 and

0800 .... 0899

TERMINAL

8 Analog inputs/outputs

0750 .... 0799

SETPOINT

10 Setpoint channel and ramp-function gen.

1000 .... 1199

FUNC

12 Drive inverter functions

1200 .... 1299

CONTROL

13 Motor open-loop/closed-loop control

1300 .... 1799

COMM

20 Communications

2000 .... 2099

ALARMS 21

Faults,

warnings,

monitoring functions"

2100 .... 2199

Grouping


TECH 22

Technological

controller (PID controller)

2200 .... 2399

Description for Binector Input (BI), Binector Output (BO), Connector Input (CI),
Connector Output (CO) and Connector Output / Binector Output (CO/BO), refer to
Section 3.1.2.3

BI Binector

Input

BO Binector

Output

CI Connector

Input

CO Connector

Output

BICO

CO/BO

Connector Output / Binector Output

Description for the command data set (CDS) and drive data set (DDS) refer to Section
3.1.3

CDS

Command data set

Data sets

DDS

Drive data set

"P" parameters can only be changed depending on the drive state. The parameter
value is not accepted if the instantaneous state is not listed in the parameter attribute
"Change state". For instance, the commissioning (start-up) parameter P0010 with the
attribute "CT" can only be changed in quick start-up "C" or ready "T" but not in run
"U".

C

Quick commissioning (start-up)

U Operation

(run)

Change state

T Ready

This parameter attribute identifies as to whether the parameter is included in the quick
commissioning (start-up) (P0010 = 1).

No

The parameter is not included in the quick commissioning (start-up)

QC.

Yes

The parameter is included in the quick commissioning (start-up)

This attribute is only of importance in conjunction with a BOP. The "Immediate"
attribute indicates that this value is already accepted when scrolling (when changing
the value with

or

). Especially parameters which are used for optimization

functions have this property (e.g. constant voltage boost P1310 or filter time
constants). On the other hand, for parameters with the attribute "After actuation", the
value is only accepted after first actuating the key

. These include, for example,

parameters where the parameter value can have different settings/meanings (e.g.
selecting the frequency setpoint source P1000).

Immediately The value becomes valid by either scrolling with

or

Active

After

actuation

The value is only accepted by pressing