Watson-Marlow MM440 User Manual

Page 200

Advertising
background image

3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

200

6SE6400-5AW00-0BP0

♦ In order that the motor can immediately establish a torque after an ON

command, the magnetizing time P0346, determined with the quick
commissioning, may not be reset. This is the reason that parameter P0346
should be checked for the weight equalization.
Typical magnetizing times for 4-pole 1LA7 motors are:

0.12 kW

50 ms

7.50 kW

300 ms

1.50 kW

100 ms

55.0 kW

700 ms

5.50 kW

250 ms

♦ The min. frequency P1080 should approximately correspond to the rated

motor slip (P1080

≈

r0330[Hz])

♦ In addition, the voltage boost should be adapted:

−

V/f mode (P1300 = 0 ... 3)

- constant voltage boost

P1310

≈

90 % (empirical value)

- voltage boost when accelerating

P1311

≈

50 % (empirical value)

−

SLVC mode (P1300 = 20)

- constant torque boost

P1610

≈

90 % (empirical value)

- torque boost when accelerating

P1611

≈

50 % (empirical value)

¾

Connecting-up the motor holding brake control

♦ Directly connected to the 1

st

relay output

Motor with
motor
holding brake

COM

NC

NO

COM

NC

NO

COM

NO

20

18

19

25

23

24

22

21

CPU

MICROMASTER 440

M

3

~

=

Fig. 3-70

Direct motor holding brake connection

Advertising