2 pid fixed setpoint (pid-ff) – Watson-Marlow MM440 User Manual

Page 178

Advertising
background image

3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

178

6SE6400-5AW00-0BP0

3.11.1.2 PID

fixed

setpoint (PID-FF)

Number: 15

Parameter range:

P2201 – P2228

Warnings -
Faults -
Function chart number:

FP3300, FP3310

Analog to the fixed frequencies (refer to Section 3.7), the PID controller has
separate programmable PID fixed setpoints. The values are defined using
parameters P2201 – P2215 and are selected using binector inputs P2220 – P2223,
P2225, P2226. The selected PID fixed setpoint is available via connector output
r2224 where it can be further processed (e.g. as PID main setpoint

→ P2253 =

2224).
3 methods are available to select the PID fixed setpoints, analog to the fixed
frequencies (Section 3.7):
¾

Direct selection

¾

Direct selection + ON command

¾

Binary-coded selection + ON command

The methods are selected using parameters P2216 – P2219, P2225, P2227.

P2216

P0701 = 15
or
P0701 = 99, P2220 = 722.0, P2216 = 1

DIN1

r2224

r0722.0

P2220

1

2,3

P2201

0

. . . .

0

. . .

.

. . . .

Fig. 3-56

Example to directly select the PID fixed frequency of fixed frequency 1 via
DIN1