3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

201

If the frequency inverter directly controls the motor holding brake using the
relay integrated in the frequency inverter, then the max. load capability of
this relay should be carefully taken into consideration in conjunction with the
voltage/current data of the holding brake. The following applies for the relay
integrated in the frequency inverter:

30 V DC / 5 A

250 V AC / 2 A

If this value is exceeded, an additional relay should, for example, be used.

♦ Indirectly connecting 1

st

relay output via an additional relay

Motor with
motor
holding brake

COM

NC

NO

COM

NC

NO

COM

NO

20

18

19

25

23

24

22

21

9

28

Output 0 V, max. 100 mA

(isolated)

Output +24 V, max. 100 mA

(isolated)

CPU

Surge

absorber

diode

24 V

0 V

Relay

MICROMASTER 440

M

3

~

=

Caution
The relay may not overload the internal 24 V power supply!

Fig. 3-71

Indirect motor holding brake connection

Hoisting gear applications

For high loads and low mechanical friction, especially when lowering a load, energy
is regenerated that can cause the DC link voltage to increase. This increase can be
prevented using dynamic braking (refer to Section 3.15.3; P1237).
In order that there is no negative effect when using dynamic braking, the following
functions should be disabled for hoisting gear applications:
♦ Vdc_max controller P1240
♦ Compound brake P1236