3 Functions

Issue 10/06

MICROMASTER 440 Operating Instructions

136

6SE6400-5AW00-0BP0

Parameter P0725 is used to define as to whether digital inputs DIN1 - DIN6 are
logical "1" when appropriately connected to 0 V or 24 V. The logical states of the
digital inputs can be de-bounced using P0724 and read-out using parameter r0722
(BICO monitoring parameter). Further, this parameter is used to parameterize
BICO for the digital inputs (refer to BICO parameterization in the following Section).
P0701 – P0706 (digital inputs 1–6) or P0707 – P0708 (analog inputs 1-2)
The possible settings of the individual inputs are listed in Table 3-11.

Table 3-11

Parameters P0701 – P0706

Parameter value

Significance

0

Digital input disabled

1 ON

/

OFF1

2

ON+reverse / OFF1

3

OFF2 – coast to standstill

4

OFF3 – quick ramp-down

9 Fault

acknowledge

10 JOG

right

11 JOG

left

12 Reverse

13

MOP up (increase frequency)

14

MOP down (decrease frequency)

15

Fixed setpoint (direct selection)

16

Fixed setpoint (direct selection + ON)

17

Fixed setpoint (binary-coded selection + ON)

25

Enable DC braking

29 External

trip

33

Disable additional frequency setpoint

99

Enable BICO parameterization


Example:
An ON/OFF1 command should be realized using digital input DIN1.

P0700 = 2

Control enabled via terminal strip (digital inputs)

P0701 = 1

ON/OFF1 via digital input 1 (DIN1)

NOTE
If an analog input (refer to Fig. 3-33) has been configured as digital input, then the
following limit values apply:

< 1.7 V DC

→ "0"

> 3.9 V DC

→ "1"