3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

85

P0310 =...

Rated motor frequency
(Nominal motor frequency in [Hz] from rating plate)
Pole pair number recalculated automatically if parameter is changed.

P0311 =...

Rated motor speed
(Nominal motor speed in [rpm] from rating plate)
Setting 0 causes internal calculation of value.
NOTE

An entry must be made for closed-loop Vector control, V/f control with FCC and
for slip compensation.

Motor magnetizing current
(this is entered as a % referred to P0305)
Motor magnetizing current as a % relative to P0305 (rated motor current).
With P0320 = 0, the motor magnetizing current is calculated using P0340 = 1 or
using P3900 = 1 - 3 (end of the quick commissioning) – and is displayed in
parameter r0331.

P0335 =...

Motor cooling

(Selects motor cooling system used)
0 Self-cooled: Using shaft mounted fan attached to motor
1 Force-cooled: Using separately powered cooling fan

2 Self-cooled and internal fan

3 Force-cooled and internal fan

P0640 =...

Motor overload factor

(Motor overload factor in [%] relative to P0305)
This defines the limit of the maximum output current as a % of the rated motor
current (P0305). This parameter is set, using P0205 for constant torque, to
150 %, and for variable torque, to 110 %.

P0700 =...

Selection of command source
(enters the command source)
0 Factory default setting
1 BOP (keypad)
2 Terminal
4 USS on BOP link
5 USS on COM link (control terminals 29 and 30)
6 CB on COM link (CB = communications module)

BOP

USS

BOP link

USS

COM link

P0700 = 2

Terminals

CB

COM link

Sequence control

Setpoint

channel

Motor

control

P0320 = ...

0.0

50.00 Hz

FU-spec.

0

150 %

2