3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

129

Example:

1. Commissioning steps with a motor:

− Carry-out commissioning at DDS1.
− Connect P0820 (P0821 if required) to the DDS changeover source

(e.g. using DIN 4: P0704[0] = 99, P0820 = 722.3).

− Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2).
− Adapt DDS2 parameters

(e.g. ramp-up / ramp-down times P1120[1] and P1121[1]).

DIN

ADC

P0820 = 722.3

SUM

setpoint

Sequence control

DIN4

AFM

RFG

Motor

control

0

1

P1120
P1121

[0]

DDS1

[1]

DDS2

[2]

DDS3

M

Gat

ing un

it

2.

Commissioning steps with 2 motors (motor 1, motor 2):

− Commission motor 1; adapt the remaining DDS1 parameters.
− Connect P0820 (P0821 if required) to the DDS changeover source

(e.g. via DIN 4: P0704[0] = 99, P0820 = 722.3).

− Changeover to DDS2 (check using r0051).
− Commission motor 2; adapt the remaining DDS2 parameters.

MM4

M1

K1

M2

K2

Motor 1

Motor 2