3.5.7 Commissioning

the

application

After the motor – drive inverter combination was commissioned using the quick or
series commissioning, in the following step parameters should be adapted and set
according to the technological requirements. As an example, the following points
should be considered:
¾

Functional requirements of the drive inverter (e.g. closed-loop process control

with PID controller)

¾

Limit values

¾

Dynamic requirements

¾

Starting torques

¾

Load surge requirement

¾

Overload

¾

Diagnostics

If the application includes a function, which is not covered by the quick or series
commissioning, then the following sections of the function description or the
parameter list should be considered.

Adapting the drive inverter to the application

The parameters designated with * offer more setting possibilities than are listed
here. Refer to the parameter list for additional setting possibilities.


Factory

setting

P0003 = 3

User access level *
1 Standard: Allows access into most frequently used parameters
2 Extended: Allows extended access e.g. to inverter I/O functions
3 Expert (For expert use only)

3.5.7.1

Serial Interface (USS)

P2010 =...

USS baud rate
Sets baud rate for USS communication.

P2011 =...

USS address
Sets unique address for inverter.

P2012 =...

USS PZD length
Defines the number of 16-bit words in PZD part of USS telegram.

P2013 =...

USS PKW length
Defines the number of 16-bit words in PKW part of USS telegram.

Possible
Settings:

4

2400

Baud

5

4800

Baud

6

9600

Baud

7 19200

Baud

8 38400

Baud

9 57600

Baud

10

76800 Baud

11

93750 Baud

12 115200 Baud

START

1

6

0

2

127