3.12.3 OFF/braking

functions

Parameter range:

P1121, P1135, P2167, P2168

P0840 – P0849

r0052 bit 02

Warnings -
Faults -

Function chart number:

-

The drive inverter and the user must respond to an extremely wide range of
situations and stop the drive. In this case, both requirements relating to operations
as well as drive inverter protective functions (e.g. electrical and thermal overload)
and man-machine protective functions have to be taken into account. As a result of
the different OFF/braking functions (OFF1, OFF2, OFF3) MICROMASTER can
flexibly respond to the requirements mentioned above.

OFF1

The OFF1 command is closely coupled to the ON command. When the ON
command is withdrawn, then OFF1 is directly activated. The drive is braked by
OFF1 with the ramp-down time P1121. If the output frequency falls below the
parameter value P2167 and if the time in P2168 has expired, then the inverter
pulses are cancelled.

t

P2168

t

P2167

Operation

act

f

OFF1

P1082

f

max

r0052 Bit02

P1121

P1082

f

P1121

t

2

1

AUS

,

down

=

t

down,AUS1

Pulse

ncellation

f

2

Fig. 3-64

OFF1