Issue 10/06

3 Functions

MICROMASTER 440 Operating Instructions

6SE6400-5AW00-0BP0

127

3.5.7.19 Command and drive data set

P0810 =...

Command data set CDS bit 0 (local / remote)
Selects the command source in which bit 0 should be read-out to select a command data
set (CDS).

t

0

1

2

3

(0:0)

BI: CDS b0 loc/rem

P0810

(0:0)

BI: CDS bit 1

P0811

t

0

1

2

3

CO/BO: Act CtrlWd2

r0055

r0055

CO/BO: Act CtrlWd1

r0054

r0054

.15

.15

.15

.15

r0050

Active CDS

Selecting CDS

approx. 4 ms

approx. 4 ms

r0050

CO: Active CDS

Changeover time

Changeover time

The currently active command data set (CDS) is displayed using parameter r0050:

r0055

bit15

r0054

bit15

1. CDS

0

0

2. CDS

0

1

3. CDS

1

0

3. CDS

1

1

r0050

0

1

2

2

Select

CDS

Active

CDS

Most frequent settings:
722.0 = Digital input 1 (P0701 must be set to 99, BICO)
722.1 = Digital input 2 (P0702 must be set to 99, BICO)
722.2 = Digital input 3 (P0703 must be set to 99, BICO)
722.3 = Digital input 4 (P0704 must be set to 99, BICO)
722.4 = Digital input 5 (P0705 must be set to 99, BICO)
722.5 = Digital input 6 (P0706 must be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, P0707 must be set to 99)
722.7 = Digital input 8 (via analog input 2, P0708 must be set to 99)

Example for CDS changeover:
CDS1: Command source via terminals and setpoint source via analog input (ADC)
CDS2: Command source via BOP and setpoint source via MOP
CDS changeover is realized using digital input 4 (DIN 4)

Steps:

1. Carry-out commissioning for CDS1 (P0700[0] = 2 and P1000[0] = 2)
2. Connect P0810 (P0811 if required) to the CDS changeover source

(P0704[0] = 99, P0810 = 722.3)

3. Copy from CDS1 to CDS2 (P0809[0] = 0, P0809[1] = 1, P0809[2] = 2)

4.

Adapt CDS2 parameters (P0700[1] = 1 and P1000[1] = 1)