5.3 Fault Detection

114

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

Converter fails to operate properly due to noise
interference.

• Review the possible solutions provided for handling noise interference.
• Review the section on handling noise interference on page 393 and check the control circuit

lines, main circuit lines, and ground wiring.

The wiring of the power supply voltage
detection circuits (

) and

the wiring of the main circuit terminals
(R/L1, S/L2, and T/L3) is not correct.

Correct the wiring.

The voltage on the power supply side is very
low.

• Check the wiring.

Correct the wiring.

• Check the load on the power supply of peripheral devices that are connected to the same power

supply line.

Reduce the load.

Digital Operator

Display

Fault Name

Details

oFA00

Option Card

Connection Error at
Option Port CN5-A

Option compatibility error

Cause

Possible Solution

The option card installed into port CN5-A is
incompatible with the converter.

Check if the converter supports the option card to be installed. Contact Yaskawa for assistance.

Digital Operator

Display

Fault Name

Details

oFA01

Option Card Fault at

Option Port CN5-A

Option not properly connected

Cause

Possible Solution

The option card connection to port CN5-A is
faulty.

Turn off the power and reconnect the option card.

Digital Operator

Display

Fault Name

Details

oFA02

Same Type of Option

Card Already

Connected

The combination of the option cards that are connected is not correct.

Cause

Possible Solution

The same option cards or the same type of
option cards are connected to CN5-A, CN5-B,
and CN5-C.

Connect the option cards correctly.

Digital Operator

Display

Fault Name

Details

to

oFA05 to

oFA06

Option Card Error

Occurred at Option

Port CN5-A

There is a fault in the option card.

,

oFA10,

oFA11

to

oFA12 to

oFA17

Option Card

Connection Error

(CN5-A)

to

oFA30 to

oFA43

Communication Option

Card Connection Error

(CN5-A)

Cause

Possible Solution

Option card or hardware is damaged.

• Cycle power to the converter.
• If the problem continues, replace the control board or the entire converter. Contact Yaskawa or

a Yaskawa representative for instructions on replacing the control board.

r1/ 11, 1/ 21, t1/ 31