Writing to multiple registers – Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 218

Advertising
background image

C.8 Message Examples

218

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

Writing to Multiple Registers

Function code 10H allows the user to write multiple converter MEMOBUS/Modbus registers with one message. This
process works similar to reading registers, in that the address of the first register to be written and the data quantity are set
in the command message. The data to be written must be consecutive so that the register addresses are in order, starting
from the specified address in the command message. The data order must be high byte then lower byte.

The following table shows an example of a message where 2000H has been set with a Multi-Function Analog Output 1
and 4000H has been set with a Multi-Function Analog Output 2 for the slave 1 converter.

If parameter values are changed using the Write command, an Enter command may be necessary to activate or save the
data depending on the setting of H5-11. Refer to

H5-11: Communications Enter Function Selection on page 212

and

Refer to

Enter Command on page 229

for detailed descriptions.

Note: Double the number of the data quantity for the number of bytes in the command message.

Command Message

Response Message (normal)

Slave Address

01H

Slave Address

01H

Function Code

10H

Function Code

10H

Starting No.

Upper

00H

Starting No.

Upper

00H

Lower

07H

Lower

07H

Data Quantity

Upper

00H

Data Quantity

Upper

00H

Lower

02H

Lower

02H

Number of Bytes

04H

CRC-16

Upper

F0H

Starting Data

Upper

20H

Lower

09H

Lower

00H

Next Data

Upper

40H

Lower

00H

CRC-16

Upper

88H

Lower

49H

TOEP_C710656_07C_2_0.book 218 ページ 2015年1月9日 金曜日 午後6時23分

Advertising