B.2 Parameter Tables

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

199

Par

ame

te

r Li

st

B

U2-64

(84DH)

Avr Input
(Voltage
Deviation) at
Previous Fault

AVR Input Shows the Avr input.

No signal
output
available

1 V

U2-65

(84EH)

Control Voltage
Reference (Vq) at
Previous Fault

Voltage Ref
(Vq)

Shows the control voltage reference (Vq) when the most recent fault
occurred.

No signal
output
available

1 V

U2-66

(84FH)

Control Voltage
Reference (Vd) at
Previous Fault

Voltage Ref
(Vd)

Shows the control voltage reference (Vd) when the most recent fault
occurred.

No signal
output
available

1 V

U3: Fault History

U3-01 to

U3-04

(90H to

93H)

First to 4th Most
Recent Fault

Fault
Message 

Displays the first to the fourth most recent faults.

No signal
output
available

U3-05 to

U3-10

(804H to

809H)

5th to 10th Most
Recent Fault

Fault
Message 

Displays the fifth to the tenth most recent faults.
After ten faults, data for the oldest fault is deleted. The most recent fault
appears in U3-01, with the next most recent fault appearing in U3-02. The
data is moved to the next monitor parameter each time a fault occurs.

No signal
output
available

U3-11 to

U3-14

(94H to

97H)

Cumulative
Operation Time at
1st to 4th Most
Recent Fault

Elapsed
Time 

Displays the cumulative operation time when the first to the fourth most
recent faults occurred.

No signal
output
available

1 h

U3-15 to

U3-20

(80EH to

813H)

Cumulative
Operation Time at
5th to 10th Most
Recent Fault

Elapsed
Time 

Displays the cumulative operation time when the fifth to the tenth most
recent faults occurred.

No signal
output
available

1 h

U4: Maintenance Monitors

U4-01
(4CH)

<4>

Cumulative
Operation Time

Drv
Elapsed
Time

Displays the cumulative operation time of the converter. The value for the
cumulative operation time counter can be reset in parameter o4-01. Use
parameter o4-02 to determine if the operation time should start as soon as
the power is switched on or only while the Run command is present. The
maximum number displayed is 99999, after which the value is reset to 0.

No signal
output
available

1 h

U4-02

(75H)

Number of Run
Commands

RUN Cmd
Counter

Displays the number of times the Run command is entered. Reset the
number of Run commands using parameter o4-13. This value will reset to
0 and start counting again after reaching 65535.

No signal
output
available

1 time

U4-03

(67H)

<5>

Cooling Fan
Operation Time

Fan
Elapsed
TIme

Displays the cumulative operation time of the cooling fan. The default
value for the fan operation time is reset in parameter o4-03. This value will
reset to 0 and start counting again after reaching 99999.

No signal
output
available

1 h

U4-04
(7EH)

Cooling Fan
Maintenance

Fan Life
Mon

Displays main cooling fan usage time as a percentage of its expected
performance life. Parameter o4-03 can be used to reset this monitor.
Replace the fan when this monitor reaches 90%.

No signal
output
available

1%

U4-05
(7CH)

Capacitor
Maintenance

Cap Life
Mon

Displays main circuit capacitor usage time as a percentage of their
expected performance life. Parameter o4-05 can be used to reset this
monitor.
Replace the capacitor when this monitor reaches 90%.

No signal
output
available

1%

U4-06

(7D6H)

Soft Charge
Bypass Relay
Maintenance

ChgCirc
Life Mon

Displays the soft charge bypass relay maintenance time as a percentage of
its estimated performance life. Parameter o4-07 can be used to reset this
monitor.
Replace the soft charge bypass relay when this monitor reaches 90%.

No signal
output
available

1%

U4-08

(68H)

Heatsink
Temperature

Heatsink
Temp

Displays the heatsink temperature.

10 V: 100

°C

1

°C

U4-09
(5EH)

LED Check

LED Oper
Check

Lights all segments of the LED to verify that the display is working
properly.

No signal
output
available

U4-13

(7CFH)

Peak Hold
Current

Current
PeakHold

Displays the highest current value that occurred during run.

1 A

No.

(Address

Hex)

Name

LCD

Display

Description

Analog

Output

Level

Unit