6.4 Cooling Fans

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

143

Per

iodic Ins

pec

tion

&

Maint

ena

nc

e

6

Cooling Fan Replacement

WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious

personal injury. Before servicing the converter, disconnect all power to the equipment. The internal capacitor remains charged even

after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the converter before

touching any components.

CAUTION! Burn Hazard. Do not touch a hot converter heatsink. Failure to comply could result in minor or moderate injury. Shut off the

power to the converter when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled

down.

NOTICE: Follow cooling fan replacement instructions. Improper fan replacement could cause damage to equipment. Make sure the fan

is facing upwards when installing the replacement fan into the converter. Replace all fans when performing maintenance to help ensure

maximum useful product life.

2A0005 to 2A0020, 4A0005 to 4A0020

Removing the Cooling Fan Finger Guard and Cooling Fan

1.

Depress the right and left sides of the fan cover tabs and pull upward. Remove the fan cover from the top of the
converter. The following figure illustrates a converter with a single cooling fan.

Figure 6.2

Figure 6.2 Remove the Cooling Fan Finger Guard: 2A0005 to 2A0020, 4A0005 to 4A0020

2.

Remove the cooling fan cartridge. Disconnect the pluggable connector and remove the fan.

Figure 6.3

Figure 6.3 Remove the Cooling Fan: 2A0005 to 2A0020, 4A0005 to 4A0020

R1000

R1000

TOEP_C710656_07C_2_0.book 143 ページ 2015年1月9日 金曜日 午後6時23分