Network termination, C.3 connecting to a network – Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 209

C.3 Connecting to a Network
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
209
MEMO
BUS/Mod
bus
Co
mmunica
tion
s
C
◆ Network Termination
The two ends of the MEMOBUS/Modbus network line have to be terminated. The converter has a built in termination
resistor that can be enabled or disabled using DIP switch S2. If a converter is located at the end of a network line, enable
the termination resistor by setting DIP switch S2 to the ON position. Disable the termination resistor on all slaves that are
not located at the network line end.
To set the DIP switch, use tweezers or a tool with a tip width of approximately 0.8 mm.
Figure C.5
Figure C.5 Communication Terminals and DIP Switch S2
DIP Switch S2
(OFF: Default)
OFF
ON
O
N
RS-422/
RS-485
R-
R+
DIP
switch
S2
Termination Resistor (1/2 W
,
110 W)
S-
S+
+
-
TOEP_C710656_07C_2_0.book 209 ページ 2015年1月9日 金曜日 午後6時23分