Ground wiring, Wiring the main circuit terminal on – Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 66

Advertising
background image

3.7 Main Circuit Wiring

66

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

Ground Wiring

Follow the precautions below when wiring the ground for one converter or a series of converters.

WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and

minimize the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment

chassis, which could result in death or serious injury.

WARNING! Electrical Shock Hazard. Be sure to ground the converter ground terminal (200 V class: ground to 100

Ω or less; 400 V

class: ground to 10

Ω or less). Improper equipment grounding could result in death or serious injury by contacting ungrounded electrical

equipment.

NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper

equipment grounding could result in converter or equipment malfunction due to electrical interference.

NOTICE: When using more than one converter, ground multiple converters according to instructions. Improper equipment grounding

could result in abnormal operation of converter or equipment.

NOTICE: If devices, such as office equipment, that is sensitive to noise are installed in the same location, separate the ground wires

and use independent grounds or noise filters to prevent noise from entering the devices through the ground wire. Otherwise, the office

equipment may fail.

Note: If other devices are installed in the same location, connect them while observing the grounding standards for each device.

Otherwise the converters or the devices may fail to operate.

Refer to

Figure 3.28

when using a converter with multiple drives. Do not loop the ground wire.

Figure 3.28

Figure 3.28 Installation Examples for a Converter and Several Drives

Wiring the Main Circuit Terminal

WARNING! Electrical Shock Hazard. Shut off the power supply to the converter before wiring the main circuit terminals. Failure to

comply may result in death or serious injury.

Wire the main circuit terminals after the terminal board has been properly grounded.

Main Circuit Connection Diagram

Refer to

Main Circuit Connection Diagram on page 52

when wiring terminals on the main power circuit of the

converter.

D1000

TOEP_C710656_07C_2_0.book 66 ページ 2015年1月9日 金曜日 午後6時23分

Advertising