B.2 Parameter Tables

184

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

d: References

Reference parameters set the value of the DC bus voltage reference.

F: Options

F parameters program the converter for communication options and to function with option cards.

C7-47

(112EH)

Adjustment Reactor
1

L1 Compensation

There is normally no need to change this parameter from
the default value.
Set this parameter to the value that is specified by the
manufacturer when using a filter such as the DC5.

Default:

<2>

Min.: 00.000
Max.: 65.000

C7-50

(113BH)

Operation Ready
ON Delay Time

Conv READY delay

Sets the delay time to turn on the Operation Ready signal
(H2- = 6).

Default: 0 ms
Min.: 0 ms
Max.: 500 ms

C7-51

(113CH)

Adjustment Reactor
2

L2 Compensation

There is normally no need to change this parameter from
the default value.
Set this parameter to the value that is specified by the
manufacturer when using a filter such as the DC5.

Default:

<2>

Min.: 00.000
Max.: 65.000

<1> This parameter is not available in model 4A0630.

<2> Default setting is dependent on parameter o2-04, Drive Model Selection.

No.

(Address

Hex)

Name

LCD Display

Description

Values

d8: DC Bus Voltage Reference

d8-01

(2B9H)

DC Bus Voltage
Reference

Vpn Volt Ref

Sets the DC bus voltage reference in volts.
Yaskawa recommends setting a value that is 1.5 times the
set value of the Power Supply Voltage (U1-54).

200 V Class

Default: 330 V
Range:300 V to
360 V

400 V Class

Default: 660 V
Range: 600 V to
730 V

No.

(Address

Hex)

Name

LCD Display

Description

Values

F4: Analog Monitor Card (AO-A3)

F4-01

(391H)

Terminal V1
Monitor Selection

AO Ch1 Select

Sets the monitor signal for output from terminal V1. Set
this parameter to the last three digits of the desired
U- monitor. Some U parameters are available only
in certain control modes.

Default: 0
Min.: 000
Max.: 408

F4-02

(392H)

Terminal V1
Monitor Gain

AO Ch1 Gain

Sets the gain for voltage output via terminal V1.

Default: 100.0%
Min.: -999.9%
Max.: 999.9%

F4-03

(393H)

Terminal V2
Monitor Selection

AO Ch2 Select

Sets the monitor signal for output from terminal V2. Set
this parameter to the last three digits of the desired
U- monitor. Some U parameters are available only
in certain control modes.

Default: 0
Min.: 000
Max.: 408

F4-04

(394H)

Terminal V2
Monitor Gain

AO Ch2 Gain

Sets the gain for voltage output via terminal V2.

Default: 50.0%
Min.: -999.9%
Max.: 999.9%

No.

(Address

Hex)

Name

LCD Display

Description

Values