D.2 European Standards

D.2 European Standards

Figure D.1

Figure D.1 CE Mark

The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in
business and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for
electronics manufacturers, and the EMC guidelines for controlling electrical noise.

This converter displays the CE mark based on the EMC guidelines and the Low Voltage Directive.

• Low Voltage Directive: 2006/95/EC
• EMC Guidelines: 2004/108/EC

Devices used in combination with this converter must also be CE certified and display the CE mark. When using
converter displaying the CE mark in combination with other devices, it is ultimately the responsibility of the user to
ensure compliance with CE standards. After setting up the device, verify that conditions meet European standards.

CE Low Voltage Directive Compliance

This converter has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low
Voltage Directive.

To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this converter with
other devices:

Area of Use

Do not use converter in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with
IEC664.

Standard Configuration Devices

Install appropriate input fuses built into the input side of the harmonic filter module to protect converter wiring and
prevent other secondary damage. Select harmonic filter module according to

Table D.1

to

Table D.3

.

Refer to

Power Ratings on page 174

for details on the converter Input Current and Rated Output Current.

NOTICE: If a fuse is open or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral

devices to identify the cause. Contact Yaskawa before restarting the converter or the peripheral devices if the cause cannot be

identified.

Table D.1 Recommended Standard Configuration Devices

Model

Harmonic

Filter

Module

Input Fuse

Three Phase Input AC Reactor

Three Phase Input Film

Capacitor

Model

Manufacturer

Fuse Rating

Ampere

(A)

SAO ELECTRIC CORP.

Nichicon Corp.

Model

Ratings

Model

Ratings

200 V Class

2A0005

EUJ71080 350GH-25ULTC

HINODE

25

300-052-260

15 A, 0.81 mH,

264 V

EM161050S0UA1HN 160 VAC, 5 uF

2A0010

EUJ71081 350GH-50ULTC

HINODE

50

300-052-261

29 A, 0.42 mH,

264 V

EM161090S0UA1HN 160 VAC, 9 uF

2A0020

EUJ71082 350GH-125ULTC

HINODE

125

300-052-262

57 A, 0.21 mH,

264 V

EM161180S0UA1HS 160 VAC, 18 uF