D.2 european standards, Ce low voltage directive compliance – Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 236
236
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
D.2 European Standards
D.2 European Standards
Figure D.1
Figure D.1 CE Mark
The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in
business and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for
electronics manufacturers, and the EMC guidelines for controlling electrical noise.
This converter displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
• Low Voltage Directive: 2006/95/EC
• EMC Guidelines: 2004/108/EC
Devices used in combination with this converter must also be CE certified and display the CE mark. When using
converter displaying the CE mark in combination with other devices, it is ultimately the responsibility of the user to
ensure compliance with CE standards. After setting up the device, verify that conditions meet European standards.
◆ CE Low Voltage Directive Compliance
This converter has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low
Voltage Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this converter with
other devices:
■
Area of Use
Do not use converter in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with
IEC664.
■
Standard Configuration Devices
Install appropriate input fuses built into the input side of the harmonic filter module to protect converter wiring and
prevent other secondary damage. Select harmonic filter module according to
to
Refer to
for details on the converter Input Current and Rated Output Current.
NOTICE: If a fuse is open or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral
devices to identify the cause. Contact Yaskawa before restarting the converter or the peripheral devices if the cause cannot be
identified.
Table D.1 Recommended Standard Configuration Devices
Model
Harmonic
Filter
Module
Input Fuse
Three Phase Input AC Reactor
Three Phase Input Film
Capacitor
Model
Manufacturer
Fuse Rating
Ampere
(A)
SAO ELECTRIC CORP.
Nichicon Corp.
Model
Ratings
Model
Ratings
200 V Class
2A0005
EUJ71080 350GH-25ULTC
HINODE
25
300-052-260
15 A, 0.81 mH,
264 V
EM161050S0UA1HN 160 VAC, 5 uF
2A0010
EUJ71081 350GH-50ULTC
HINODE
50
300-052-261
29 A, 0.42 mH,
264 V
EM161090S0UA1HN 160 VAC, 9 uF
2A0020
EUJ71082 350GH-125ULTC
HINODE
125
300-052-262
57 A, 0.21 mH,
264 V
EM161180S0UA1HS 160 VAC, 18 uF